Plan ahead High Patch available CVSS 8.1
OpenPLC Runtime flaw lets attackers create admin accounts without logging in
CISA ICS AdvisoriesAutonomy Logic, OpenPLC Runtime · critical manufacturing, energy, transportationCVE-2026-126088
What happened. CISA reports a race condition in OpenPLC Runtime 4.2.4 and earlier. Several simultaneous requests can create unauthenticated admin accounts. The vendor fix is OpenPLC Runtime 4.3.0 or later.
Who is affected. Users of Autonomy Logic OpenPLC Runtime 4.2.4 and earlier in critical manufacturing, energy, transportation and water and wastewater.
What to do. Update to OpenPLC Runtime 4.3.0 or later. Check first whether you run version 4.2.4 or earlier.
When to act. Plan ahead: Sites running OpenPLC Runtime 4.2.4 or earlier should update to 4.3.0 before the next maintenance window.
Editor's reading
Forasset ownerOT security lead
- Purdue level
- L2
- L1
Why: OpenPLC Runtime runs the control logic of a programmable logic controller (PLC), which places it at the controller level (L1), with its web interface used from L2.
- Are you exposed?
Check your asset inventory for OpenPLC Runtime 4.2.4 or earlier and for any reachable OpenPLC web interface.
- If you cannot fix it yet
- Restrict access to the OpenPLC web interface to known engineering hosts.
- Keep the runtime off the internet and behind a firewall.
- Review the list of user accounts and remove any you do not recognise.
- Watch for
- Bursts of simultaneous requests to the OpenPLC account-creation page.
- New admin accounts on OpenPLC that no one on your team created.
- ATT&CK for ICS
- T0859Valid Accounts
Inferred from the facts above, not stated by the source. Check it against your own site before acting.
Source: CISA ICS Advisories (opens cisa.gov)
Published by Industrial Cyber Brief · Editor: Abhinav Roy · Drafted by AI and checked by code: how this is made · Corrections
More on Manufacturing Energy and power Transportation CVE-2026-126088