Six unpatched flaws found in Danfoss refrigeration controller firmware

The Register - securityDanfoss · refrigeration

What happened. A researcher at Midnight Blue says he found six zero-day flaws in Danfoss AK-SM800A firmware 5.3.2 in under an hour. The Centre for Cybersecurity Belgium warns attackers could take control without credentials, keep access after resets, or disable controllers.

Who is affected. Sites running the Danfoss AK-SM800A refrigeration controller, firmware 5.3.2 was examined. The source names refrigeration as the sector.

What to do. Check whether you run Danfoss AK-SM800A firmware 5.3.2, and keep those controllers off the internet and reachable only from trusted hosts until Danfoss provides a fix.

When to act. Plan ahead: Operators running Danfoss AK-SM800A controllers: check exposure and firmware before the next maintenance window.

Editor's reading

Forasset ownerOT security leadvendor/integrator

Purdue level
  • L2
  • L1
Level 2, supervisory control (HMIs, SCADA, engineering workstations); Level 1, basic control (PLCs, RTUs, safety controllers)

Why: The AK-SM800A is a refrigeration controller with network-reachable firmware, which places it at the control level (L1) and the supervisory level (L2) where it is managed.

Are you exposed?

Search your asset inventory for Danfoss AK-SM800A units, note their firmware versions, and check whether their web interface is reachable from the internet or the office network.

If you cannot fix it yet
  • Block internet and IT-network access to the controller's web interface at the firewall.
  • Allow connections only from known engineering or management hosts.
  • Require multi-factor authentication on any remote-access path used to reach the controllers.
Watch for
  • Web requests to the controllers from unknown hosts, especially unusually long inputs or repeated crashes and reboots.
  • Unexpected controller restarts, loss of cooling control, or configuration changes after a reset.
ATT&CK for ICS
T0866Exploitation of Remote ServicesT0814Denial of Service

Inferred from the facts above, not stated by the source. Check it against your own site before acting.

Share

Source: The Register - security (opens theregister.com)

Published by Industrial Cyber Brief · Editor: Abhinav Roy · Drafted by AI and checked by code: how this is made · Corrections

More on Danfoss Food and agriculture

More from this briefing

Read the full issue Executive report Get it by email

You confirm by email: look for a message from brief@mail.girder.in, in junk too if it is not in your inbox. You can leave in one click from any briefing. See today's issue · Privacy

Follow the Brief: Telegram · Bluesky · X