London data centre outage traced to PLC wiring fault, not attackers
Industrial CyberGoogle · energy
What happened. Google's final report says a London power failure took its europe-west2-b zone offline. Voltage sensing inputs on the programmable logic controllers (PLCs) that start the generators were wired on the line side of an isolated utility breaker, so the generators never started.
Who is affected. Google europe-west2-b zone in London. Banks and court video links were disrupted, including Revolut, Lloyds Banking Group and HSBC.
What to do. Review how your generator-start control logic and sensing wiring are tested, including when a utility breaker is isolated for repairs.
Why it matters to your site. Use it to check that backup-power control logic is tested under real isolation and fault conditions, not only normal ones.
When to act. For awareness: Plant engineers: review PLC sensing wiring and power-loss logic; no new threat, so schedule for routine review.