Industrial Cyber Briefby Girder · AI-powered industrial cyber security news
LiveSubscribe

From the briefing of

Plan ahead Critical Check your exposure CVSS 9.8

Unauthenticated flaw in Danfoss AK-SM 8xxA controllers allows remote code execution

CISA ICS AdvisoriesDanfoss · Commercial FacilitiesCVE-2026-129713

What happened. A stack-based buffer overflow in a web handler lets remote attackers send crafted HTTP/S POST requests without logging in. This can corrupt memory, restart the webserver and potentially run code with webserver privileges. CVSS score 9.8. The fix is planned for version 5.5.x.

Who is affected. Sites running Danfoss AK-SM 8xxA Series controllers up to and including version 5.4.0, mainly in Commercial Facilities worldwide.

What to do. Check whether you run Danfoss AK-SM8xxA version 5.4.0 or earlier, and plan the upgrade to 5.5.x when Danfoss releases it.

When to act. Plan ahead: Refrigeration and building operators running AK-SM 8xxA up to 5.4.0: restrict web access and plan the 5.5.x update.

Editor's reading

Forasset ownerOT security lead

Purdue level
  • L2
  • L1
Level 2, supervisory control (HMIs, SCADA, engineering workstations); Level 1, basic control (PLCs, RTUs, safety controllers)

Why: AK-SM 8xxA is a supervisory controller with a web interface that manages refrigeration and building equipment, placing it at the control and supervisory levels.

Are you exposed?

Search the asset inventory for Danfoss AK-SM 8xxA units at version 5.4.0 or earlier and check whether their web interface is reachable from other networks.

If you cannot fix it yet
  • Restrict HTTP/S access to the controller web interface to known management hosts only.
  • Remove any direct internet exposure of the controller and place it behind a firewall.
  • Keep Strict Mode enabled and do not disable it.
Watch for
  • Unexpected HTTP/S POST requests to the controller's CGI handlers from unknown sources.
  • Repeated webserver restarts on AK-SM controllers, which may indicate exploitation attempts.
ATT&CK for ICS
T0866Exploitation of Remote Services

Inferred from the facts above, not stated by the source. Check it against your own site before acting.

Share

Source: CISA ICS Advisories (opens cisa.gov)

Published by Industrial Cyber Brief · Editor: Abhinav Roy · Drafted by AI and checked by code: how this is made · Corrections

More on Danfoss CVE-2026-129713

More on Danfoss

More from this briefing

Read the full briefing

Briefing
Also send me
You confirm by email: look for a message from brief@mail.girder.in, in junk too if it is not in your inbox. Change your choices or leave in one click from any email. Privacy

Follow the Brief: Telegram · Bluesky · X