Plan ahead Medium Patch available CVSS 6.1
ABB ACS380-E drive can leave User Lock open after closing
ABB PSIRTABB · ManufacturingCVE-2026-103236
What happened. A firmware defect in ABB ACS380-E drives can leave User Lock open after closure with specific settings and the default Adaptive Programming application. Parameters stay open without the passcode until restart. CVSS 6.1. A software update is available.
Who is affected. Users of ABB ACS380-E4C02C drives running firmware 3.2.0.7 or 3.2.0.9, in manufacturing.
What to do. Check whether your drives run ABB ACS380-E4C02C firmware 3.2.0.7 or 3.2.0.9, and apply the ABB software update.
When to act. Plan ahead: ACS380-E drive owners on affected firmware: apply the software update at the next routine maintenance window.
Editor's reading
Forasset owner
- Purdue level
- L1
Why: The ACS380-E is a variable speed drive, which sits at the controller level (L1).
- Are you exposed?
Check the firmware version of each ACS380-E4C02C drive and whether User Lock is used with the default Adaptive Programming application.
- If you cannot fix it yet
- Restart affected drives after closing User Lock, so the parameters are locked again.
- Restrict access to drive parameters to authorised engineers and keep drives on a segmented network.
- Watch for
- Drive parameter changes made by users who do not hold the User Lock passcode.
- Parameter access to ACS380-E drives from unexpected hosts.
Inferred from the facts above, not stated by the source. Check it against your own site before acting.
Source: ABB PSIRT (opens search.abb.com)
Published by Industrial Cyber Brief · Editor: Abhinav Roy · Drafted by AI and checked by code: how this is made · Corrections
More on ABB Manufacturing CVE-2026-103236